at 1 to 2 footcandles. If adjusted to the extreme
right (MAX position), the ON relay will close at
approximately 100 footcandles. (There is a 2 - 4
second built-in delay).
IMPORTANT: The potentiometer allows you to
adjust a turn ON at 1 to 100 footcandles. OFF will
be 3 times the ratio of the ON foot candle level.
Light level adjustment is the same for both
circuits.
IMPORTANT NOTES CONCERNING THE
PHOTOCELL INPUT:
1. An ON event must be scheduled prior to sun-
set in order for the photocell to activate circuit
#1. Timer can then be scheduled OFF and
later ON again before sunrise for any desired
days.
2. Circuit #2 is directly controlled by photocell
and light level adjustment. It is not governed
by timer or the manual override.
3. Photocell can be wired up to 500 feet from
timer using 2 wire, #18 to #22 AWG, between
input terminal and photocell.
4. Do not put excessive pressure on potentiome-
ter. Use thumb and forefinger or small screw-
driver to adjust for light level. Avoid shorting
screwdriver to upper board.
5. Light level adjustment operates only with Tork
Photocell Model EPC1.
KEY FUNCTIONS
DAY/MONTH: Press to advance the day in the
CLK mode. Press to advance the Month in the
DATE mode.
HOUR/DATE: Press to set the Hours in the CLK
mode and in the Schedule SET mode. Press to
advance Date in the DATE mode.
3
LIGHT LEVEL ADJ.
MIN MAX
DAY
MONTH
HOUR
DATE
MIN
YEAR
OVER-
RIDE
MODE SP DAY ON/OFF ENTER
MIN/YEAR: Press to set the Minute in the CLK
mode and in the Schedule SET mode. Press to
advance Year in the DATE mode.
OVERRIDE: Press to alter the Load status and/or
to Override scheduled event on circuit #1 only.
MODE: Press to advance to next mode without
affecting the scheduled memory information.
Sequence is: RUN, CLK, DATE, schedule SET. In
the SET mode, unit automatically reverts to
the RUN mode if no entries are made for 5
minutes.
SP DAY: Press during RUN mode to execute the
“SPECIAL DAY’ schedule everyday. LCD will dis-
play D in upper right corner. Pressing SP DAY
again will toggle the unit back to normal 7 day
program operation.
ON/OFF: Pressing each time will select an ON or
an OFF. Multiple OFF’s may be scheduled to can-
cel override ON’s.
ENTER: Press to store the displayed information
into memory. Information will not be stored
until ENTER is pressed.
NOTE: During settings, each press of the key will
advance one number. For rapid advance, hold
key in.
SELECT AM/PM OR 24 HOUR
MILITARY FORMAT:
Upon powering up the unit the LCD will display
the model number 100. The LCD will next display
12H which is an automatic (AM/PM) format.
Press ENTER to keep AM/PM format or press
HOUR key to alter to 24 hour (Military) format and
then press ENTER.
4