Step 5:
Set the warning period for 1 or 5 minutes using
switch # 4. See table for desired timing.
Step 6 (optional):
If it is desirable to have the auxiliary load on
momentarily only (4 seconds i.e. for bell or other
warning signal) place the
special switch
down in
the momentary position (see below).
Step 7:
Remote ON/OFF momentary push buttons can be
connected at the remote input terminal between C
& ON to activate extended time, and C & OFF to
disable extended time.
MAIN SWITCH
CONFIGURATION
SPECIAL SWITCH FOR
AUXILIARY LOAD ONLY
UP (Main) Position:
ON for same 1 or 5 minute
period as set by main switch
#4 (see above).
DOWN (Momentary) Position:
Auxiliary load is on for 4 seconds only,
but main load is on for the warning period set
by main switch #4 (see above).
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
TIME
SET
1
2
3
*
*
*
*
*
*
*
ON
4
1/2 HR
1 HR
1-1/2 HR
2 HR
6 HR
9 HR
12 HR
TEST
OFF
OFF
OFF
OFF
ON
ON
ON
ON
*Switch 4 (ON) – 5 Minute Warning Period
*Switch 4 (OFF) – 1 Minute Warning Period
ON
SW1
OFF
1234
MAIN
MOM
C5
C4
TORK
®
MLI-142(B) 1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
WIRING DIAGRAMS
Important Note:
When the Lighting Delay Switch is first activated –
A. If a time switch is connected and is set to ON,
the main load will remain ON.
B. If no
time switch is used or if one is connected
but is set to OFF, the main load will turn ON for
10 minutes. At the end of the 10 minute period,
the warning circuit turns on for 4 seconds, 1
minute, or 5 minutes. The main load will remain
ON for the 1 or 5 minute warning period. If an
extension of time is required for the main load,
press the remote ON button momentarily, the
warning circuit will turn off, and the main load
will remain on for an additional 1/2 - 12 hour
extension of time.
OFF
ON
NO C NC
REMOTE
INPUT
TIME SWITCH
INPUT
AUX. OUTPUT
TERMINALS
MAIN LOAD OUTPUT
TERMINALS
INPUT POWER
MOMENTARY
PUSH-BUTTON SWITCH
AUX
LOAD
LOAD
H N N 120
208
240
277
VAC
NC NC NO NO CC
H
N
H
N
H
N
TORK TIME SWITCH
OUTPUT TERMINALS
C ON OFF
DO NOT APPLY
VOLTAGE
CAUTION: Turn power off at main circuit prior
to installation or when servicing this unit.